MAG6416Ⅱ 32-channel Fire Linkage Module

Features

● This module is the interface between network PA system and fire center.;
● When receiving the alarm signal sent by the fire center, it will activate the network PA system corresponding working area automatically and enter the override status of the emergency broadcasting;
● Each machine has 32 fire trigger channels, and each channel alarm zone can be any combination through the host setting;
● Each alarm channel includes routing fault detection function, and can troubleshooting system line automatically;
● The same system can have multiple machines connected to the network, and can extend control area at random.

  • Introduction
  • Specification

MAG6416Ⅱ 32-channel Fire Linkage Module

1.Setup indicator

When the parameters of this module cannot be found, (such as IP is not clear) press the Mode button. The indicator will light.

2.Alarm signal input interface

CH1-CH9,1 channel to 9 channel for alarm signal input interface, COM for common terminal

3.Alarm signal input interface

CH10-CH18,10 channel to 18 channel for alarm signal input interface, COM for common terminal

4.Dip switch

Mode: When the parameters of this module cannot be found, (such as IP is not clear) press the Mode button.The indicator will light, and the machine parameters restore the following specific parameters:

IP:192.168.16.2GATE:192.168.16.1Mask Code:255.255.255.0

Main server IP:192.168.16.250  Standby server IP:192.168.16.251

After setting, dialmodeto restore the previous configuration.

Note: In the same network only one machine of the same type can be setmode, otherwise it will have IP conflict.

Check: Line detection enable to switch. The machine has a 32-channel line fault detection function, dial the switch to open the line detection (channel independent switch setting refer to the fourth section "fire channel line detection function configuration"). If you want to use line detection,the channel which needed to open the line detection need to need to configure the 47K pull-down resistor box.

Note: When the module issued a drop of sound is relatively long, indicating that the external line is not connected, when the issue of the sound is more rapid, indicating that is the alarm sound.

H / L: When theinput logic setting switch is set toH, it is the level trigger mode; when thesetting switch is set to L, it is short-circuit trigger mode.

5.Alarm signal input interface

CH19-CH27, 19-channel to 27-channel alarm signal input interface, COM is common.

6.Alarm signal input interface

CH28-CH32, 28-channel to 32-channel alarm signal input interface, COM is common.

Note: Alarm signal input interface can be input with a positive polarity signal of 5V-24V or the short circuit signal of 0Ω-5K impedance.

7.SC1、SC2 short circuit output

As long as there is an alarm signal input (any one or more), SC1, SC2 short circuit output.

8.485 communication interface

A, B for the RS485 communication interface. It can be used to communicate with other third party systems to implement alarm triggers (using this function has to contact our technical staff).

485 protocol format:

Frame header + source address + destination address + frame number + length + function code + data + check code

The header is FE FC

Source address, destination address, frame number, function code for 1 byte, length, check code for 2 bytes, higher one is in front and the length does not contain the header

The generator polynomial of the CRC check is: X16 + X15 + X2 + 1

The address of this alarm module is: 0xFE

Function code meaning:

0x66 set all zones alarm, followed by 32 bytes of data, data 0 indicating that the alarm revoked, 1 for alarm

0x67 set a single zone alarm, followed by a byte channel number and a byte of state data, channel number 0-31 for 1-32 channel, the alarm state values are the same as above.

9.Network indicator

When the module drops the indicator lights green; when the module is connected successfully via the network,the indicator lights red.

Package Dimension

190×40×230mm

Machine Dimension

173×23×210mm

Gross Weight

1.5kg

Net Weight

1.0kg

Relate Products

  • POE1028 SNR Self-adaptive PoE Network SensorPOE1028 SNR Self-adaptive PoE Network SensorJuly 28, 2020The device will automatically adjust the volume of the broadcast sound to make it larger than the on-site ambient sound; otherwise, when the on-site ambient sound is detected too much smaller than the...view
  • MAG6265 IP Network Video Intercom TerminalMAG6265 IP Network Video Intercom TerminalNovember 8, 2017The MAG6265 is a network visual intercom device for bi-directional intercom with the visual broadcast intercom management host. It can be used in LAN or WAN (depending on the actual situation) via net...view
  • MAG6505 Network industrial intercom terminalMAG6505 Network industrial intercom terminalAugust 30, 2017MAG6505 network industrial intercom terminal is a full-digital A/D conversion signal processor based on TCP / IP transmission protocol, dual network redundancy design, for wall mount use at any place....view
Leave a Message Email Us

we will contact you within 24 hours.

Related News
  • Smart Light Pole System for Smart CitiesSmart Light Pole System for Smart CitiesMarch 25, 2024It is a very large and comprehensive management system, which should not only meet the needs of public security management, urban management, traffic management, and emergency command, but also take into account the demand for image monitoring in the disaster and accident early warning and safety production monitoring.view
  • Invitation to 2020 SCO International Investment and Trade ExpoInvitation to 2020 SCO International Investment and Trade ExpoOctober 10, 2020Abstract: DSPPA sincerely invites you to attend SCO International Investment and Trade Expo 2020 in Qingdao on 16-18, Oct..DSPPA is willing to extend our sincere invitation to you to attend SCO Intern...view
  • Tel:+86 020 37166520
  • Email:export@dsppa.com
  • Address:No.1 Xiahe Rd, Jianggao Town, Baiyun District, Guangzhou, Guangdong, China
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Visit our cookie policy to learn more.
Reject Accept