MP9822EII is an uninterruptible power supply device with dual conversion, single-phase input and single-phase output. The product is compact in size while with high efficiency and high reliability, which is user-friendly. It is an ideal choice for users in the field of finance, telecommunication, government, transportation, manufacturing and education. This device is used together with MP9822AII and battery box MP9822BII, among which MP9822AII is optional; MP9822BII is the battery box. Users can equip the devices according to the backup time requirements. And the quantity of the device is at least one and no more than three.
Model | MP9822EII | |
Nominal capacity | 3kVA/2700W | |
Input | Input mode | One-way grounding |
Voltage range | (180±5)VAC~(250±5)VAC | |
The power factor | ≥0.99 | |
The bypass voltage | (180±5)VAC~(250±5)VAC | |
Output | Output way | One-way grounding |
The rated voltage | AC220V ① | |
The power factor | 0.9 | |
Voltage accuracy | ±2% | |
Frequency | 1. Same as input frequency (46Hz ~ 54Hz); 2. 50Hz(AC power frequency >54Hz or mains power frequency<46Hz); | |
Overload capacity | 100%±5%<load ≤105%±5% overload alarm; 105%±5%< load | |
Conversion time | AC power←→battery 0 ms AC power←→bybass < 4 ms | |
Crest factor | 3:1 | |
EMC | Electro-Static discharge(ESD) | IEC61000-4-2 Level4 |
Radiated electromagnetic field immunity(RS) | IEC61000-4-3 Level3 | |
Electrical fast transit(EFT) | IEC61000-4-4 Level4 | |
Surge(Surge) | IEC61000-4-5 Level4 | |
MP9822BII battery | Battery input voltage | 96VDC |
Built-in battery number | N.A. | |
Built-in battery type | 12V/7AH Sealed maintenance-free lead-acid batteries | |
Backup time | Full load ≥5 minutes | |
Charging current | 5.5A | |
Working environment | Working temperature | 0℃~40℃ |
Working humidity | 20%~90%(no condensation) | |
Working altitude | Less than 1,000 meters. Over 1000 m, 1% reduction for every 100 m increase | |
Storage temperature | -15℃~45℃ | |
Packing size, mm | 568x550x223 | |
Machine dimensions, mm | 476x482.6x88 | |
Gross weight, kg | 12 | |
Net weight, kg | 10.5 | |
MP9808R PA System Digital AM/FM TunerNovember 30, 20161 Power switch(1 is power on and the “power LED” is on ) 2 Power indicator 3 Up keys 4 Auto keys 5 Band keys 6 Down keys 7 Mono keys 8 Memo keys 9 Display screen 10 M1 to +10 Locatio...view
MP9820S PA System 10-channel Switching PowerMarch 16, 2017view
MP2000 Classical Series Power AmplifierNovember 30, 2016This class b amplifier is designed for commercial and industrial public address applications. Rack mount design in 2U type and rated power is 350W /450W/650W.Both balanced and unbalanced line inputs a...viewwe will contact you within 24 hours.
【DSPPA】 Editor of Double National StandardDecember 22, 2021In May 2010, Technical Code for Public Address System Engineering (GB50526-2010), the world’s first national standard for public engineering with DSPPA as the chief editor, was issued by the Ministry of Housing and Urban-Rural Development of PRC, establishing China's independent intellectual property right in the field of Public Address (short for PA) system.view
Brief Introduction of Public Broadcasting SystemMarch 29, 2019Because of the limited sound energy produced by natural sound sources (such as voice speech, singing, musical instrument playing, sound reproduction, etc.), the sound pressure level decreases with the...view