MP9822EII is an uninterruptible power supply device with dual conversion, single-phase input and single-phase output. The product is compact in size while with high efficiency and high reliability, which is user-friendly. It is an ideal choice for users in the field of finance, telecommunication, government, transportation, manufacturing and education. This device is used together with MP9822AII and battery box MP9822BII, among which MP9822AII is optional; MP9822BII is the battery box. Users can equip the devices according to the backup time requirements. And the quantity of the device is at least one and no more than three.
Model | MP9822EII | |
Nominal capacity | 3kVA/2700W | |
Input | Input mode | One-way grounding |
Voltage range | (180±5)VAC~(250±5)VAC | |
The power factor | ≥0.99 | |
The bypass voltage | (180±5)VAC~(250±5)VAC | |
Output | Output way | One-way grounding |
The rated voltage | AC220V ① | |
The power factor | 0.9 | |
Voltage accuracy | ±2% | |
Frequency | 1. Same as input frequency (46Hz ~ 54Hz); 2. 50Hz(AC power frequency >54Hz or mains power frequency<46Hz); | |
Overload capacity | 100%±5%<load ≤105%±5% overload alarm; 105%±5%< load | |
Conversion time | AC power←→battery 0 ms AC power←→bybass < 4 ms | |
Crest factor | 3:1 | |
EMC | Electro-Static discharge(ESD) | IEC61000-4-2 Level4 |
Radiated electromagnetic field immunity(RS) | IEC61000-4-3 Level3 | |
Electrical fast transit(EFT) | IEC61000-4-4 Level4 | |
Surge(Surge) | IEC61000-4-5 Level4 | |
MP9822BII battery | Battery input voltage | 96VDC |
Built-in battery number | N.A. | |
Built-in battery type | 12V/7AH Sealed maintenance-free lead-acid batteries | |
Backup time | Full load ≥5 minutes | |
Charging current | 5.5A | |
Working environment | Working temperature | 0℃~40℃ |
Working humidity | 20%~90%(no condensation) | |
Working altitude | Less than 1,000 meters. Over 1000 m, 1% reduction for every 100 m increase | |
Storage temperature | -15℃~45℃ | |
Packing size, mm | 568x550x223 | |
Machine dimensions, mm | 476x482.6x88 | |
Gross weight, kg | 12 | |
Net weight, kg | 10.5 | |
MP2500 Classical Series Power AmplifierNovember 30, 2016This class b amplifier is designed for commercial and industrial public address applications.view
MP9813C Broadcast PartitionerAugust 16, 2022MP9813C broadcast partitioner has 2 channels of inputs and 10 channels of outputs. With override function, it can input emergency broadcast signal. Besides, it has 10 zone selection buttons with indep...view
MP2000 Classical Series Power AmplifierNovember 30, 2016This class b amplifier is designed for commercial and industrial public address applications. Rack mount design in 2U type and rated power is 350W /450W/650W.Both balanced and unbalanced line inputs a...viewwe will contact you within 24 hours.
Speaker System in Conference Room, Key Point ThreeMarch 29, 2019The third key point: microphone digital audio processorA good microphone digital audio processor (commonly known as automatic mixer) can greatly improve the sound quality and transmission gain of the ...view
DSPPA | Debut at ISLE 2025: Exploring New AV HorizonsMarch 11, 2025Abstract: DSPPA made a strong debut at ISLE 2025, presenting innovative audiovisual solutions to a global audience.view