Items |
PAVA120B |
||
|
Rated power output |
120W (Note: please connect high impedance speaker within this load) |
||
|
Rated voltage output |
100V |
||
|
Sensitivity |
Microphone |
5mv(±1mv) |
|
|
Line input |
1VRMS(±100mv) |
||
|
SNR |
Microphone |
≥70dB |
|
|
Line input |
≥80dB |
||
|
Frequency response |
Microphone |
100Hz~10KHz(±3dB) |
|
|
Line input |
80Hz~15KHz(±3dB) |
||
|
The ratio of source electromotive force |
≥12dB |
||
|
Total harmonic distortion |
≤0.5% |
||
|
Tone adjustment range |
±11±2 dB |
||
|
Rated power consumption |
250W |
||
|
Main and standby amplifier switching time |
No intermittent |
||
|
Battery life of 12AH (two batteries in series form 24V) |
2H (voice evacuation works normally) |
||
|
Battery specs |
Size |
≤150×100×100mm ( 2 pcs) |
|
|
Voltage |
12V;(use two in series to make 24V) |
||
|
Power supply |
AC220V-230V/50Hz |
||
|
Packing size |
570×470×271mm |
||
|
Machinedimensions |
500×400×180mm |
||
|
Gross weight |
17KG |
||
|
Net weight |
15KG (without batteries) |
||
PAVA2240 All in One Compact Wall-Mounted Voice Evacuation SystemNovember 14, 2018PAVA2240 is the host of the compact wall-mounted voice evacuation system. With built-in 240W digital amplifier, not only can it send out warning and alarm, but also support handhold microphone to make voice evacuation. It can manage emergency alarming, fiview
PAVA4400FM Wallmount Fireman MicrophoneApril 12, 2021PAVA4400FM is a wall-mounted fireman microphone used with PAVA4600 4-zone integrated voice evacuation system host. It supports the control of PAVA4600 and real-time microphone monitoring; powered by P...view
PAVA2200 Fireman MicrophoneDecember 19, 2018PAVA2200 is the wall mount Fireman Microphone used with PAVA2240, 2-zone Voice Evacuation System. It could accept control from PAVA2240 and supports real-time monitoring. 24V Network power supply is n...viewwe will contact you within 24 hours.
Sound Effect Principle of Surface Mount Ceiling SpeakersNovember 6, 2020Surface mount ceiling speakers are also known as ceiling speakers. Large-sized ceiling speakers have a larger diaphragm diameter, and the volume of air that is pushed will become larger and larger, an...view
What are the Requirements for Loudspeaker Configuration in Public Adress Speaker Systems?April 25, 2019Usually, the background noise of office corridor is about 48-52 dB, and that of supermarket is about 58-63 dB, and that of busy section is about 70-75 dB. Considering that the scene may be very confus...view