PAVA4600 is an integrated voice evacuation system host. With built-in 600W digital amplifier, not only can it send out warning and alarm, but also support handhold microphone to make voice evacuation. It can manage emergency alarming, fire alarm announcement and background music playing for 4 zones. It is an ideal application for small shopping malls, office building and sports venues.
PAVA4600 Voice Alarm PA System Configuration

Note: The PAVA4600 host can be cascaded with at most three extended hosts, and supports two connection modes: closed and star.
|
Items |
Parameters |
||
|
Rated output power |
600W (Note: Please use the constant speakers within the power range) |
||
|
Rated output voltage |
100V |
||
|
Sensitivity |
MIC |
5mv(±1mv) |
|
|
AUX IN |
1VRMS(±100mv) |
||
|
SNR |
MIC |
≥70dB |
|
|
AUX IN |
≥80dB |
||
|
Frequency response |
MIC |
100Hz~10KHz(±3dB) |
|
|
AUX IN |
80Hz~15KHz(±3dB) |
||
|
Ratio of source emf. |
≥12dB |
||
|
THD |
≤1% |
||
|
Tone adjustment range |
±11±2 dB |
||
|
Rated power consumption |
850W |
||
|
AC-DC power supply switching time |
No interruption |
||
|
12AH battery (two batteries in series into 24V) endurance |
2H (normal emergency voice broadcast) |
||
|
Battery |
Size |
(2 pcs) |
|
|
Voltage |
12V; (two in series into 24V) |
||
|
Working Voltage |
AC220V-230V/50Hz |
||
|
Package dimensions |
820×470×275mm |
||
|
Machine dimensions |
750×400×180mm |
||
|
Gross weight |
20kg |
||
|
Net weight |
19kg(without batteries) |
||
PAVA4400FM Wallmount Fireman MicrophoneApril 12, 2021PAVA4400FM is a wall-mounted fireman microphone used with PAVA4600 4-zone integrated voice evacuation system host. It supports the control of PAVA4600 and real-time microphone monitoring; powered by P...view
PAVA2200FM Voice Evacuation MicrophoneJune 10, 2021PAVA2200FM is a wall-mounted MIC used in conjunction with PAVA120B Integrated Voice Evacuation System Host. It supports the control of PAVA120B Host and the real-time monitoring of MIC, while PAVA120B...view
PAVA2200 Fireman MicrophoneDecember 19, 2018PAVA2200 is the wall mount Fireman Microphone used with PAVA2240, 2-zone Voice Evacuation System. It could accept control from PAVA2240 and supports real-time monitoring. 24V Network power supply is n...viewwe will contact you within 24 hours.
DSPPA kicking off the internationalization of the National StandardNovember 25, 2016The kick-off meeting of internationalization of the National Standard – Technical code of public address system engineering (GB 50526) was held in the 798 art zone, Beijing on May 24, 2014. This meeting is hosted by Guangzhou DSPPA Audio Co. Ltd, and tenview
Development History of Conference System IndustrySeptember 28, 2022With the rapid development of international information technology, people's requirements for the efficiency and quality of the meeting are increasingly high, the conference system has also experi...view