EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating status and recording of operating logs. It meets the relevant standard of “EN54-16 Voice Alarm Control and Indicating Equipment”. The broadcasting system can be used for fire emergency broadcasting, daily service broadcasting and background broadcasting; this system is positioned as a small emergency broadcasting system, mainly used in small shopping malls, small office buildings and exhibition halls, etc.
PAVA9500 is an 8-zone amplifier host with main/backup switching function in the EN54-16 system, and is designed to be 2U high, with backup amplifier, timed audio sources, 2 microphone inputs, 4 analog inputs, 1 line output and a fire emergency broadcast panel; supports the total power of up to 500W; holds 8 zone outputs, with the total power of 500W for all zones.
PAVA9500E is an 8-zone expansion amplifier with main/backup switching function in the EN54-16 system, and is designed to be 2U high, with backup amplifier, 2 microphone inputs, 4 analog inputs and 1 line output; supports the total power of up to 500W; holds 8 zone outputs, with the total power of 500W for all zones.



Model | PAVA9500 | PAVA9500E | ||
Rated Output Power | ≥500W (100V) | |||
Input Sensitivity | EMC MIC | 20mV 600Ω | —— | |
MIC | 5±0.5mV 10kΩ | |||
LINE | 1000±100mV 10kΩ | |||
Harmonic Distortion | EMC MIC | <1% 1kHz | —— | |
MIC | 1%1khz | |||
LINE | <1% 1kHz | |||
Frequency Response | EMC MIC | 80Hz-15kHz (±3dB) | —— | |
MIC | 1%1khz | |||
LINE | 50Hz-18kHz (±3dB) | |||
S/N Ratio | EMC MIC | >75dB (A-Weighted) | —— | |
MIC | 1%1khz | |||
LINE | >80dB (A-Weighted) | |||
EMC Line Auxiliary Output | Output Voltage | 1000mV | 1000mV | |
Frequency Range | 80Hz-15kHz (±3dB) | 80Hz-15kHz (±3dB) | ||
Harmonic Distortion | <1% 1kHz | <1% 1kHz | ||
System Connection Control Contact Output/Input | System Fault Relay Output | Short circuit, no voltage | ||
Emergency Mode Relay Output | Short circuit, no voltage | |||
Fire Reset Input | Short circuit, t≥0.5S, no voltage | |||
8-Channel Dry Contact Output | Short circuit, no voltage | |||
8-Channel Dry Contact Input | Short Circuit Mode | Short circuit input, no voltage | ||
Level Mode | 3.3V~24V | |||
Voice Message | Data Format | WAV | —— | |
Storage Type | SD card | —— | ||
Retention Time | >10 years | —— | ||
Working Power | AC | AC220V-240V/50-60Hz | ||
DC | DC 24V/17A | |||
Package Dimensions (L*W*H) | 625×635×165mm | |||
Machine Dimensions (L*W*H) | 483*430*88mm | |||
Gross Weight | 14kg | 13.3kg | ||
Net Weight | 12.05kg | 11.75kg | ||
PAVA9009 Fireman MicrophoneJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...view
PAVA9003 Power Management UnitMarch 5, 2026The PAVA9003 Power Management Unit is designed for use with EN54-16 systems. It provides backup power supply for the PAVA9500 amplifier host, PAVA9500E expansion amplifier, and PAVA9425E expansion amp...view
PAVA9002 Fire Alarm Audio Notification System Network Control TerminalJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...viewwe will contact you within 24 hours.
DSPPA | Get Ready for Innovations at Booth 7L500, ISE 2025December 12, 2024Abstract: Discover the future of audio at Booth 7L500 during ISE 2025.view
DSPPA | Conference & Pro Sound Systems for Large ProjectsNovember 21, 2022Abstract: Here gathers a variety of DSPPA conferences and pro-sound projects for international summits and major sports events.view