Model | PAVA9002 | |
Remote Paging Microphone - Network Control Terminal | Remote Paging Sending Mode Interface (sending audio signals to the host) | TX RM1-2 (TX RM green indicator light on the front panel is on) |
Input Sensitivity (RJ45 Interface) | ±3000mV (±300mV) | |
RM Bus Power Supply | DC48V (±5V) | |
Expansion Amplifier - Network Control Terminal | Expansion Amplifier Receiving Mode Interface (receiving audio signals from the host) | RX EXT1-2 (RX EXT green indicator light on the front panel is on) |
Input Sensitivity (RJ45 Interface) | ±1500mV (±150mV) | |
Host - Network Control Terminal | Host Receiving Mode Interface (receiving audio signals from the remote paging microphone) | RX RM1-2 (RX RM green indicator light on the front panel is on) |
Input Frequency Response | 100Hz~12kHz (±3dB) | |
Sending Mode Interface (sending audio signals to the expansion amplifier) | TX EXT1-2 (TX EXT green indicator light on the front panel is on) | |
Input Frequency Response | 50Hz~16kHz (±3dB) | |
Distortion (Within Frequency Response) | <1% | |
S/N Ratio A-Weighted | ≥76dB | |
Operating Voltage Range | DC21V-28V | |
Power Supply | Rated power supply DC24V/2.5A (±3V), backup power supply DC24V/2.5A | |
Host Sending Mode Interface Output Level (RJ45 Interface) | ±1500mV (±150mV) | |
Host Sending Mode Microphone Interface Output Level (RJ45 Interface) | ±3000mV (±300mV) | |
Adapter Operating Power | AC110V-240V 50/60Hz | |
Operating Temperature | -20℃~+50℃ | |
Operating Humidity | 20%~80% relative humidity, non-condensing | |
Package Dimensions | 295*241*115mm | |
Machine Dimensions | 165*115*55mm | |
Gross Weight | 2.0kg | |
Net Weight | 0.65kg | |
PAVA9425E 4-Zone Expansion Amplifier with Main / Backup SwitchingJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...view
PAVA9500E 8 ZoneS Voice Alarm Fire Evacuation System Expansion Amplifier with Main/Backup SwitchingJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...view
PAVA9003 Power Management UnitMarch 5, 2026The PAVA9003 Power Management Unit is designed for use with EN54-16 systems. It provides backup power supply for the PAVA9500 amplifier host, PAVA9500E expansion amplifier, and PAVA9425E expansion amp...viewwe will contact you within 24 hours.
The application field of Internet technology conference systemDecember 28, 20211. Remote business meeting application of conference systemThe most common and extensive application of electronic conference business is suitable for some large group companies and wholly foreign-own...view
Application of Smart PA SystemMarch 30, 2021Ⅰ. Smart PA system applicationsThe smart PA system is one of the indispensable infrastructures of every school. Although the video technology and network technology have been developing rapidly in re...view