EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating status and recording of operating logs. It meets the relevant standard of “EN54-16 Voice Alarm Control and Indicating Equipment”. The broadcasting system can be used for fire emergency broadcasting, daily service broadcasting and background broadcasting; this system is positioned as a small emergency broadcasting system, mainly used in small shopping malls, small office buildings and exhibition halls, etc.
PAVA9425E is a 4-zone expansion amplifier with main/backup switching function in the EN54-16 system, and is designed to be 2U high, with 2 microphone inputs, 4 analog inputs and 1 line output; features a backup amplifier module; supports the total power of up to 1000W; holds 4 zone outputs, with the total power of 1000W for all zones.



Model | PAVA9425E | ||
Rated Output Power | ≥1000W (100V) | ||
Input Sensitivity | EMC MIC | —— —— | |
MIC | 5±0.5mV 10kΩ | ||
LINE | 1000±100mV 10kΩ | ||
Harmonic Distortion | EMC MIC | <1% 1kHz | |
MIC | 1%1khz | ||
LINE | <1% 1kHz | ||
Frequency Response | EMC MIC | 80Hz-15kHz (±3dB) | |
MIC | 1%1khz | ||
LINE | 50Hz-18kHz (±3dB) | ||
S/N Ratio | EMC MIC | >75dB (A weighted) | |
MIC | 1%1khz | ||
LINE | >80dB (A weighted) | ||
EMC LINE AUX OUT | Output Voltage | 1000mV | |
Frequency Range | 80Hz-15kHz(±3dB) | ||
Harmonic Distortion | <1% 1kHz | ||
System Connection Control Contact Output/Input | System Fault Relay Output | Short circuit, no voltage | |
Emergency Mode Relay Output | Short circuit, no voltage | ||
Fire Reset Input | Short circuit, t≥0.5S, no voltage | ||
4-Channel Dry Contact Output | Short circuit, no voltage | ||
4-Channel Dry Contact Input | Short Circuit Mode | Short circuit input, no voltage | |
Level Mode | 3.3V~24V | ||
Working Power | AC | AC220V-240V/50-60Hz | |
DC | DC 24V/34A | ||
Package Dimensions (L*W*H) | 625×635×165mm | ||
Machine Dimensions (L*W*H) | 483*430*88mm | ||
Gross Weight | 14kg | ||
Net Weight | 12.05kg | ||
PAVA9008 16 Zones Remote Paging MicrophoneJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...view
PAVA9002 Fire Alarm Audio Notification System Network Control TerminalJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...view
PAVA9009 Fireman MicrophoneJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...viewwe will contact you within 24 hours.
Another Symbolic Project of DSPPA - Guangzhou Metro Operation CenterNovember 23, 2016November 16th, was destined to be a memorable day.This day,some of our colleagues tried their best to install the PA system in Guangzhou Metro Operation Center.DSPPA PA System applied in Guangzhou Metro Operation Centerview
The Function and Characteristic of PreamplifierApril 29, 20211. The basic function of preamplifierThe preamplifier is the connection device between various audio source equipment (including ordinary audio sources such as CD players, tuners, decks, MP3 players a...view